InBuilding - Buildings
InBuilding is for offices, hospitals and schools. From real data it works out two things: electricity used outside the building's operating hours, and whether every room meets the standard for its kind. An operating theatre is judged at 20-24 °C, a vaccine fridge at 2-8 °C, a classroom at no more than 1000 ppm CO₂.

Choosing the kind of building
When installing InBuilding, pick Perkantoran (office), Rumah sakit (hospital) or Sekolah (school). The choice sets the devices that come with it, the default operating hours and the room kinds offered. It can be changed later in Profil Gedung (building profile).

Pages
- Dashboard: current load, energy, share of energy outside operating hours, rooms within standard, a card per room and per load, recommendations, alarms.
- Ruangan (rooms): every room against the standard for its kind, its value now, the share of time it met the standard in the chosen range, and its worst excursion.
- Monitoring: device monitor and automation.
- Analitik (analytics): CO₂ and temperature trends, each load's energy outside operating hours, recommendations.
- Notifikasi (notifications): recommendations and the alarm log.
- Profil Gedung: building type, operating hours, each room's kind, and loads that run 24 hours.

The standard for each kind of room
| Room kind | Standard | Reference |
|---|---|---|
| Workspace, meeting room | 22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppm | ASHRAE 55, SNI 03-6572 |
| Lobby & common area | 22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppm | ASHRAE 55, SNI 03-6572 |
| Server room | 18-27 °C, RH ≤ 60% | ASHRAE TC 9.9 |
| Inpatient ward | 21-24 °C, RH ≤ 60%, CO₂ ≤ 1000 ppm | ASHRAE 170 |
| Operating theatre | 20-24 °C, RH 20-60% | ASHRAE 170 |
| ICU | 21-24 °C, RH 30-60% | ASHRAE 170 |
| Isolation room | 21-24 °C, RH ≤ 60%, pressure ≤ -2.5 Pa | ASHRAE 170, CDC |
| Vaccine fridge | 2-8 °C | Vaccine cold chain (WHO) |
| Waiting room & clinic | 22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppm | ASHRAE 55, 62.1 |
| Classroom, laboratory, library, hall | 22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppm | ASHRAE 62.1, SNI 03-6572 |
In an operating theatre, ICU, isolation room or vaccine fridge, any excursion is marked Perlu tindakan (act now).
Setting the building profile
Open InBuilding, then Profil Gedung.
Choose the Jenis gedung (building type). The operating hours change to that type's default.
Set the Jam operasional (operating hours): start, end and days. A load's energy outside these hours counts as waste.
Under Jenis ruangan (room kinds), pick the kind of each room sensor. The first guess comes from the device name: "Ruang Operasi 1" becomes an operating theatre.
Under Beban 24 jam (24-hour loads), tick the loads that must run day and night, such as ward AC or a server room. Their energy does not count as waste.
Press Simpan profil gedung (save building profile).

Only a Tenant Admin can save the building profile.
Devices
Each load needs its own energy meter (IBX-EM-1P or IBX-EM-3P). A room sensor (IBX-RS) sends temperature, humidity, co2, pm25 and occupancy. An isolation room's sensor also sends pressure_diff: the pressure difference to the corridor in Pa. A vaccine fridge only needs a temperature sensor (temperature).
Its pages can be rearranged: open the solution and press Edit layout.