InBuilding is for offices, hospitals and schools. From real data it works out two things: electricity used outside the building's operating hours, and whether every room meets the standard for its kind. An operating theatre is judged at 20-24 °C, a vaccine fridge at 2-8 °C, a classroom at no more than 1000 ppm CO₂.

The InBuilding dashboard of a hospital

Choosing the kind of building ​

When installing InBuilding, pick Perkantoran (office), Rumah sakit (hospital) or Sekolah (school). The choice sets the devices that come with it, the default operating hours and the room kinds offered. It can be changed later in Profil Gedung (building profile).

The building type choice in the InBuilding install panel

Pages ​

  • Dashboard: current load, energy, share of energy outside operating hours, rooms within standard, a card per room and per load, recommendations, alarms.
  • Ruangan (rooms): every room against the standard for its kind, its value now, the share of time it met the standard in the chosen range, and its worst excursion.
  • Monitoring: device monitor and automation.
  • Analitik (analytics): CO₂ and temperature trends, each load's energy outside operating hours, recommendations.
  • Notifikasi (notifications): recommendations and the alarm log.
  • Profil Gedung: building type, operating hours, each room's kind, and loads that run 24 hours.

The Ruangan page with each room's compliance

The standard for each kind of room ​

Room kindStandardReference
Workspace, meeting room22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppmASHRAE 55, SNI 03-6572
Lobby & common area22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppmASHRAE 55, SNI 03-6572
Server room18-27 °C, RH ≤ 60%ASHRAE TC 9.9
Inpatient ward21-24 °C, RH ≤ 60%, CO₂ ≤ 1000 ppmASHRAE 170
Operating theatre20-24 °C, RH 20-60%ASHRAE 170
ICU21-24 °C, RH 30-60%ASHRAE 170
Isolation room21-24 °C, RH ≤ 60%, pressure ≤ -2.5 PaASHRAE 170, CDC
Vaccine fridge2-8 °CVaccine cold chain (WHO)
Waiting room & clinic22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppmASHRAE 55, 62.1
Classroom, laboratory, library, hall22-27 °C, RH ≤ 65%, CO₂ ≤ 1000 ppmASHRAE 62.1, SNI 03-6572

In an operating theatre, ICU, isolation room or vaccine fridge, any excursion is marked Perlu tindakan (act now).

Setting the building profile ​

  1. Open InBuilding, then Profil Gedung.

  2. Choose the Jenis gedung (building type). The operating hours change to that type's default.

  3. Set the Jam operasional (operating hours): start, end and days. A load's energy outside these hours counts as waste.

  4. Under Jenis ruangan (room kinds), pick the kind of each room sensor. The first guess comes from the device name: "Ruang Operasi 1" becomes an operating theatre.

  5. Under Beban 24 jam (24-hour loads), tick the loads that must run day and night, such as ward AC or a server room. Their energy does not count as waste.

  6. Press Simpan profil gedung (save building profile).

    The Profil Gedung page

Only a Tenant Admin can save the building profile.

Devices ​

Each load needs its own energy meter (IBX-EM-1P or IBX-EM-3P). A room sensor (IBX-RS) sends temperature, humidity, co2, pm25 and occupancy. An isolation room's sensor also sends pressure_diff: the pressure difference to the corridor in Pa. A vaccine fridge only needs a temperature sensor (temperature).

Its pages can be rearranged: open the solution and press Edit layout.

How to install: Installing a solution.